Product overview

Product model: 983
Nominal diameter: DN15~65mm
Nominal pressure: PN0.01~1.6MPa
Operating temperature: ≤350℃
Main material: forged steel, stainless steel, titanium alloy steel, chromium molybdenum steel, low temperature steel
Drive mode: manual
Design specification: GB/T 9093
Structure length: GB/T 12250
Threaded connection: ISO 228
Flanged connection: JB/T 79,GB 9113,ANSI B16.34
Test and inspection: GB/T 13927

983 Inverted Bucket Steam Trap product details

983 Inverted Bucket Steam Trap Basic Information

Working principle of 983 inverted bucket steam trap produced and sold by Baigang valve group:  Inverted hanging (set) bucket steam trap It is the use of condensed water and steam density difference principle of work, the internal structure is connected by the lever system upside down bucket to overcome the steam pressure switch inverted bucket trap inside is an inverted bucket for the liquid Bit-sensitive parts, inverted bucket opening down. When the device is started, air and low temperature condensate appear in the pipe. At this time, the trap is fully open, and the air and low temperature condensate are quickly discharged, and the device quickly raises the temperature. When steam enters the inverted bucket, the inverted bucket produces upward buoyancy, and the inverted bucket connects the lever to drive the valve to close the valve. Inverted bucket has a small hole to open the air automatically, as part of the steam discharged from the hole, the other part of the steam condensate, inverted bucket loses its buoyancy to sink, inverted bucket connected to the valve lever to open the valve lever. When the steam into the inverted bucket again, the valve closed again, work cycle, intermittent drainage.


Nominal pressure
PN16
PN25
PN40
Anti-air resistance function
Vents self-control
Vents self-control
Vents self-control
PMA maximum allowable pressure 1.6MPa@38 ℃
2.5MPa@38 ℃ 4.1MPa@38 ℃
PMO maximum working pressure 1.3MPa@315 ℃ 2.0MPa@200 ℃ 2.5MPa@200 ℃
TMA maximum allowable temperature
425 ℃@1.1MPa 425 ℃@1.1MPa 425 ℃@2.6MPa
TMO maximum operating temperature
425 ℃@1.1MPa 425 ℃@1.1MPa 425 ℃@2.6MPa


983 Inverted Bucket Steam Trap main dimensions

Product number Nominal diameter (mm) Connection method Working pressure (MPa) The maximum allowable temperature Dimensions Weight (kg)
L H1 H2 W
980 15-20 Thread 0.01-1.0 350 128 76 70 96 2.2
981 15-25 0.01-1.6 350 128 76 100 96 2.8
982 15-25 0.01-1.6 350 170 96 137 145 7.0
983 25-32 0.01-1.6 350 202 121 193 180 14.0
884 32-40 0.01-1.6 350 235 152 212 203 23.0
885 32-50 0.01-1.6 350 260 232 222 228 26.0
816 50 0.01-1.6 350 302 214 242 202 42.0
881F 15-25 Flange 0.01-1.6 350 195 76 100 96 5
882F 20-25 0.01-1.6 350 230 96 137 145 10
883F 25-32 0.01-1.6 350 270 121 193 180 18
983F 40-50 0.01-1.6 350 320 121 193 180 18
884F 32-50 0.01-1.6 350 320 152 212 203 27
885F 40-50 0.01-1.6 350 350 232 222 228 29
816F 65-80 0.01-1.6 350 400 214 242 302 45